Allen Bradley Plc Slot Numbering

  1. Allen Bradley Plc Slot Numbering Software
  2. Allen Bradley Plc Port Number
  3. Allen Bradley Plc Slot Numbering Machine
  4. Allen Bradley Plc Slot Numbering Tool
  5. Allen Bradley Plc Slot Numbering Chart

There are a number of addressing schemes used by PLC manufacturers. Let’s take a quick look at how memory locations (including hardware I/O) are accessed with RSLogix 500. Along the way, let’s define some terms.

INSTRUCTION – RSLogix’s command language is comprised of “instructions”. An XIC (it looks like a normally open contact –] [– ) is an instruction. A timer is an instruction. A few of the most common instructions are described below.

Allen-Bradley Bulletin 1746 SLC™ I/O Modules are part of our SLC 500 control platform. Rockwell Automation announces that as of August 31, 2018, additional Bulletin 1746 I/O modules will be discontinued and no longer available for sale. Here is where some confusion comes in. Because the Rockwell numbering system starts with 0, and the processor resides in Slot 0, our example bit is actually in slot 5. Our bit 3 is actually the 4th bit. We could also describe the bit as “Slot 5, position 4”. You will have to learn to transpose these ways of describing a bit back and forth.

BIT – an address within the PLC. It can be an input, output or internal coil, among others.

In RSLogix, there are a couple of ways to show the address of a bit. The default is:

[type]:[word]/[bit]

For example, an address that references an output of a MicroLogix 1100 is O:0/0. That is:

O:0/5 means that it is a physical output.
O:0/5 means that it uses Slot 0 (in the case of the 1100, this output is onboard)
O:0/5 means that it is the fifth output on the PLC.

By the way, don’t get the capital “O” confused with a zero.

RUNG – A section of the PLC ladder program that terminates in an output function of some type. Just like in an electrical ladder diagram, a rung has some type of output that is turned on or turned off by the preceding entities in the rung. The first rung in a ladder program is always 0000.

HARDWIRED INPUT – a physical connection to the PLC from an input device (switch or sensor, etc.).

Allen-Bradley uses the capital letter “I” to designate a hardwired input. An address that describes an input on an SLC 500 is I:4/0.

Similar to the output structure,

I:4/0 means that it is a physical input.
I:4/0 means that it uses Slot 4 (the 5th slot in the rack).
I:4/0 means that it is the first input on the card.

Don’t get the capital “I’s” confused with ones.

Allen Bradley Plc Slot Numbering Software

Bradley

HARDWIRED OUTPUT – a physical connection from the PLC to an output device (relay or pilot light, etc.) As was said above, an address that references an output of an SLC 500 is O:5/0.

INTERNAL COIL
This is a programmable bit used to simulate a relay within the PLC. The internal coil has no connection to the outside world. It does not connect to an output card. Internal coils are used to store information. The “contacts” of this “relay” can then be used multiple times in other parts of the program.

In RSLogix, the “B3” (binary) file is commonly used for all the internal coils. There are many other words in other files that have bits you can use as internal coils, but we are going to stick with the B3 file for our application.

B3:0/0 means that it references an internal Binary file
B3:0/0 means that it uses the first word in the table
B3:0/0 means that it is the first bit in the word.

Note that, unlike the Output and Input files, you have to use the file number in the address. In this case, the default file number is 3.

TIMER
A timer is a programmable instruction that lets you turn on or turn off bits after a preset time.

The two primary types of timers are TON for “timer on delay” and TOF for “timer off delay”.

Timers in A-B SLC and MicroLogix processors use file 4 for their timers.

Numbering

T4:0 means that it references an internal Timer file
T4:0 means that it uses the first timer in the table

The address T4:0 simply refers to the timer. Each timer has bits that turn on after the timing function is complete. You can address this bit by simply putting a “/DN” after the timer address. DN stands for “done”.

Slot

For example, if timer T4:0 is a TON (timer on delay), then the bit T4:0/DN will turn on after the timer has reached its preset value.

COUNTER
A counter is a programmable instruction that lets you turn on or turn off bits after a preset count has been reached.

There are different types of counters available in the RSLogix, but the CTU (counter up) instruction covers everything we will talk about here.

Counters in A-B SLC and MicroLogix processors use file 5.

C5:0 means that it references an internal Counter file
C5:0 means that it uses the first counter in the table

The address C5:0 simply refers to the counter. Each counter has bits that turn on after the counting function is complete. You can address this bit by simply putting a “/DN” after the counter address. DN stands for “done”.

For example, if counter C5:0 is a CTU (counter up), then the bit C5:0/DN will turn on after the counter has reached its preset value.

–] [– Normally Open Contact
When used with a hardwired input, this instruction is off until there is a voltage applied to the input. The bit address then goes high, or on, and the instruction becomes “true.” It works the same way when it has the same address as an internal coil, except that the coil must be turned on by logic in the program.

Allen-Bradley calls these normally open contacts “XIC”, or “eXamine If Closed” instruction.

An XIC instruction can reference a hardwired input, a hardwired output, an internal coil or a timer done bit, among others.

–]/[– Normally Closed Contact
This is an inverted normally open contact.

When used with a hardwired input, this instruction is “true” until there is a voltage applied to the input. It then goes low, or off, and becomes “false.”

It also can be used with an internal coil, becoming true when the coil is off and becoming false when the coil is on.

Allen-Bradley calls these normally closed contacts “XIO”, or “eXamine If Open” instructions.

-( )- Output Coil
When used with a hardwired output, this function is off until the logic in the program allows it to turn on. It then becomes “true”, and will energize the device that is wired to the respective output.

Allen Bradley Plc Port Number

If it is used as an internal coil, it will toggle the instructions associated with it. That is, it will close a normally open instruction and open a normally closed instruction.

Allen-Bradley calls these outputs “OTE”, or “OutpuT Energize”.

An OTE may be used with a hardwired output or an internal coil.

Allen Bradley Plc Slot Numbering Machine

TRUE – A state that indicates an instruction is allowing logic to “flow” through it.

Allen Bradley Plc Slot Numbering Tool

Also, if the logic in a rung turns on the output of the rung, then the rung is said to be true.

Allen Bradley Plc Slot Numbering Chart

FALSE – Without stating the obvious, this is the opposite of true.

Excerpted from PLC Programming with RSLogix 500

[00:00] In this example, we are going to learn how to connect to a control logix, through another control logix PLC, using ENBT modules. This is important when you have PLCs on two different subnets and your Ignition gateway is only on one of those subnets. By chaining the PLCs together, Ignition should be able to talk to both of the PLCs at the same time. The idea is fairly simple. From Ignition, we're going to go into our first control logix PLC through an ENBT module. We're then going to go out a separate ENBT module, into our second control logix PLC, where we'll be able to hit the processor. So in order to make this happen, we need to tell Ignition the route from the first PLC to the second PLC, and we do that with a connection path. If we look down here in the bottom right, here's the connection path that will make this setup work. Let's look at the connection path in a little more detail. First, when we come into the first control logix PLC, we need to go to the backplane. So the first value of our connection path is a one, to represent going to the backplane. From there, we are going to go out slot three, to represent going out the second ENBT module. So the next value is a three. We then want to go to the ethernet port of the second PLC. So we specify that with the number two. We then need to specify the IP address of the slot number on the second control logix PLC that holds the ENBT module. In this example, that IP address is 192.168.0.56. From there, we need to go to the backplane of the second control logix PLC, which again is a value of one, and then we want to end at the processor in slot zero. So we finish our connection path with a value of zero. This connection path tells Ignition how to route from the first PLC all the way to the second PLC. Let's take a look at a realtime example of this in Ignition. We are first going to want to come to the devices page in the configuration section of our gateway webpage. We then want to click the Create new Device link. We then need to select a driver for the end result PLC that we are connecting to, which in this case is a control logix. So I'm going to select the logix driver to connect to it. We then want to scroll down and hit the Next button. We then need to give our device a name. I'm going to name mine control logix ENBT and then the host name property will be the IP address of the first PLC that we're connecting to. In my case, it's 10.20.4.62. Finally we need to specify our connection path to the processor in the second PLC, in the connection path property. First, I need to go to the backplane of our first PLC, so I'm going to start with a value of one. My second ENBT module is then located in slot two, so my second number is going to be a two. We are then going to go to the ethernet port of the second PLC, so again, that's another two. We then need to specify the IP address of the second control logix ENBT module. In this case, my IP address is 10.20.4.65. From there, we then need to go to the backplane of the second control logix device, a one, and lastly we need to end in the processor, which is in slot zero. So this whole list of numbers would be our entire connection path, and once we have that in there, we can scroll down and click the Create New Device button. Once it has connected, and is given a chance to browse the second PLC, we can then scroll down, and go to our Quick Client under OPC Connections, expand the OPC-UA Server folder, and find our device with all of our tags inside of it.